How to Design Under/Over Frequency Relay Model in MATLAB SIMULINK | Dr. J. A. Laghari
Main summary
Key takeaways
Summary
Dr. J. A. Laghari demonstrates how to model under- and over-frequency protection in MATLAB/Simulink. Frequency relays are identified as ANSI/IEEE device 81: 81U/81L denotes under-frequency protection, while 81O/81H denotes over-frequency protection.
Main concepts
- Under-frequency relays operate when system frequency falls below a set threshold. They can protect generators and transformers or initiate load shedding to help preserve system stability.
- Over-frequency relays operate when frequency rises above a threshold and can protect a generator from rotor overspeed.
- The tutorial describes example two-stage generator protection settings:
- Under-frequency: At 48.5 Hz, trip the grid circuit breaker; at 47.5 Hz, trip the generator circuit breaker.
- Over-frequency: At 51.5 Hz, trip the grid circuit breaker; at 52.5 Hz, trip the generator circuit breaker.
- The relay model’s frequency-measurement and trip-logic block is not part of the standard Simulink library. The presenter attributes it to Professor Rodney Tan.
Model components and setup
The demonstrated model includes:
- A three-phase programmable voltage source, configured for 400 V line-to-line, a 0° phase angle, and a nominal frequency of 50 Hz.
- A programmable frequency step variation, with settings for the step size and when the variation begins and ends.
- Three-phase measurement blocks at Buses A and B, configured to measure phase-to-ground voltage.
- Two three-phase series RLC loads. The load at Bus B is the important load to be disconnected by the relay.
- Scopes for observing bus voltages and relay frequency.
- A frequency-relay subsystem containing a phase-locked loop (PLL) to measure frequency, a MATLAB Function block for trip logic, a clock, and a scope.
- A three-phase circuit breaker that starts closed and waits for an external trip signal.
Relay settings include the nominal frequency, under- and over-frequency limits as percentages, and a ride-through time delay. At 50 Hz, a 1% deviation corresponds to 0.5 Hz; for example, a 5% under-frequency setting gives a threshold of 47.5 Hz. The presenter advises keeping the PLL settings as supplied in the model. An additional 20 ms delay represents mechanical relay movement.
Simulation procedure and examples
- Set the source’s nominal frequency and choose a frequency step variation, including its magnitude and start and end times.
- Configure the relay’s nominal frequency, percentage threshold, and ride-through delay.
- Run the simulation and inspect the PLL frequency trace to confirm when the threshold is crossed.
- Check the Bus B voltage scope to see whether the relay issued a trip command and disconnected the load.
The tutorial demonstrates three cases:
- 5% under-frequency: The source frequency steps down by 3 Hz, from 50 Hz to 47 Hz, between 0.1 and 0.8 seconds. With a relay threshold of 47.5 Hz and a ride-through delay of 0.2 seconds, the frequency reaches the threshold at about 0.16 seconds, and the load is disconnected at about 0.38–0.39 seconds.
- 2% under-frequency: The threshold is changed to 49 Hz and the ride-through delay to 0.1 seconds. A −1.5 Hz step takes the frequency to 48.5 Hz, and the relay disconnects the load at about 0.255 seconds.
- 2% over-frequency: The source step is changed to +1.5 Hz, taking the frequency above the 51 Hz threshold to about 51.5 Hz. The over-frequency relay operates and disconnects the load.
The presenter notes that the model can be adapted to other frequency settings and delays, incorporated into other power-system models, or used for studies such as under-frequency load shedding.
Speakers and sources featured
- Dr. J. A. Laghari — presenter and narrator.
- Professor Rodney Tan — credited by the presenter as the developer of the custom frequency-relay model or block; not heard speaking in the subtitles.
- ANSI/IEEE C37.2 — standard cited for frequency-relay device number 81.