How to Design Under/Over Frequency Relay Model in MATLAB SIMULINK | Dr. J. A. Laghari

Main summary

Key takeaways

Educational

Summary

Dr. J. A. Laghari demonstrates how to model under- and over-frequency protection in MATLAB/Simulink. Frequency relays are identified as ANSI/IEEE device 81: 81U/81L denotes under-frequency protection, while 81O/81H denotes over-frequency protection.

Main concepts

  • Under-frequency relays operate when system frequency falls below a set threshold. They can protect generators and transformers or initiate load shedding to help preserve system stability.
  • Over-frequency relays operate when frequency rises above a threshold and can protect a generator from rotor overspeed.
  • The tutorial describes example two-stage generator protection settings:
    • Under-frequency: At 48.5 Hz, trip the grid circuit breaker; at 47.5 Hz, trip the generator circuit breaker.
    • Over-frequency: At 51.5 Hz, trip the grid circuit breaker; at 52.5 Hz, trip the generator circuit breaker.
  • The relay model’s frequency-measurement and trip-logic block is not part of the standard Simulink library. The presenter attributes it to Professor Rodney Tan.

Model components and setup

The demonstrated model includes:

  • A three-phase programmable voltage source, configured for 400 V line-to-line, a 0° phase angle, and a nominal frequency of 50 Hz.
  • A programmable frequency step variation, with settings for the step size and when the variation begins and ends.
  • Three-phase measurement blocks at Buses A and B, configured to measure phase-to-ground voltage.
  • Two three-phase series RLC loads. The load at Bus B is the important load to be disconnected by the relay.
  • Scopes for observing bus voltages and relay frequency.
  • A frequency-relay subsystem containing a phase-locked loop (PLL) to measure frequency, a MATLAB Function block for trip logic, a clock, and a scope.
  • A three-phase circuit breaker that starts closed and waits for an external trip signal.

Relay settings include the nominal frequency, under- and over-frequency limits as percentages, and a ride-through time delay. At 50 Hz, a 1% deviation corresponds to 0.5 Hz; for example, a 5% under-frequency setting gives a threshold of 47.5 Hz. The presenter advises keeping the PLL settings as supplied in the model. An additional 20 ms delay represents mechanical relay movement.

Simulation procedure and examples

  1. Set the source’s nominal frequency and choose a frequency step variation, including its magnitude and start and end times.
  2. Configure the relay’s nominal frequency, percentage threshold, and ride-through delay.
  3. Run the simulation and inspect the PLL frequency trace to confirm when the threshold is crossed.
  4. Check the Bus B voltage scope to see whether the relay issued a trip command and disconnected the load.

The tutorial demonstrates three cases:

  • 5% under-frequency: The source frequency steps down by 3 Hz, from 50 Hz to 47 Hz, between 0.1 and 0.8 seconds. With a relay threshold of 47.5 Hz and a ride-through delay of 0.2 seconds, the frequency reaches the threshold at about 0.16 seconds, and the load is disconnected at about 0.38–0.39 seconds.
  • 2% under-frequency: The threshold is changed to 49 Hz and the ride-through delay to 0.1 seconds. A −1.5 Hz step takes the frequency to 48.5 Hz, and the relay disconnects the load at about 0.255 seconds.
  • 2% over-frequency: The source step is changed to +1.5 Hz, taking the frequency above the 51 Hz threshold to about 51.5 Hz. The over-frequency relay operates and disconnects the load.

The presenter notes that the model can be adapted to other frequency settings and delays, incorporated into other power-system models, or used for studies such as under-frequency load shedding.

Speakers and sources featured

  • Dr. J. A. Laghari — presenter and narrator.
  • Professor Rodney Tan — credited by the presenter as the developer of the custom frequency-relay model or block; not heard speaking in the subtitles.
  • ANSI/IEEE C37.2 — standard cited for frequency-relay device number 81.

Rate this summary

Your feedback will help improve summaries.

Improve this summary

Reprocess with a stronger model when the summary feels incomplete or inaccurate.

Pro

Translate summary in another language

Pro

Ask questions to this video

Chat for follow-up questions, clarifications, and source-backed answers.

Coming soon

Share this summary

Original video