WEBI'MARS Volet 1 l'air à l'hôpital -
Main summary
Key takeaways
Main ideas / lessons from the webinar
Air quality and airborne infection risk in healthcare
Webinar purpose and structure
- The organizers ran a short survey after a prior webinar to select new topics.
- Because the theme “environment / environmental management” is broad, they split it into three webinars during March.
- Today’s webinar topic: risks associated with air quality in healthcare facilities.
- The audience can ask questions:
- in writing (question tab), or
- orally (raise hand), with dedicated time at the end of presentations.
Presentation 1 — Mr. Bouillon (Setup)
Standards and engineering of air distribution in operating rooms
1) Regulatory/standards framework mentioned
Operating-room air hygiene is governed by several standards, emphasizing risk-based classification, cleanroom behavior, and air distribution:
- ISO 14644 series (cleanroom classification & risk analysis)
- ISO 14644-1: particle classification (examples mentioned: ISO 5, ISO 7, ISO 8).
- ISO 14644-2: risk analysis to assign/increase classification “point” values and determine sampling strategy.
- EN 14644-3 (referred to as replaced/updated)
- Noted as shifting toward approaches that account for medical devices, including contamination assessment and sampling.
- EN 16890
- Relevant in the context of ventilation air / filtration (subtitle text referenced “heroic distribution,” i.e., ventilation/duct/airflow considerations).
- “Air hygiene / air quality Bible”
- EN 13050(351) is described as extremely important and linked to overall air hygiene/quality expectations and costs (subtitle text was noisy but the emphasis was clear).
2) Engineering objective of a cleanroom / operating room
A cleanroom must:
- Control contaminants, both
- specific particles and
- microbiological contamination
- Control
- entry of people and materials
- hygiene rules
- Limit contamination from outside into the controlled zone.
3) How air handling works (outside air → treatment → operating room)
Key mechanisms and risks
A) Outside air intake risk
- Air handling units typically draw in outside air, treat it, and distribute it to operating rooms.
- Outside air inlets are not always pollution-free.
- Example: a laboratory fume hood near the intake can lead pollutants to “re-enter” the duct/AHU system and then reach rooms.
- Lesson: upstream intake sources must be controlled and adequately separated in building design.
B) Air treatment & distribution
- Air handling units treat air for hygiene (not just temperature/humidity).
- Air may be:
- 100% extracted to outside, or
- partially recycled/remixed with outside air.
- Recycling introduces additional issues (including anesthetic gas concentration and contamination control).
C) Single vs centralized AHUs (maintenance complexity)
- Dedicated AHU for one operating room is simpler.
- Central AHU serving multiple rooms:
- increases maintenance complexity
- shutting down can affect multiple rooms simultaneously.
4) Filtration requirements: why very fine filters are necessary
- Key quantitative lesson: 99.9% of particles are smaller than 1 micron.
- Therefore, high-performance filtration is required to stop aerosols.
- Example context: urban outdoor air can have very high particle counts.
- Implication: filtration efficiency must be extremely high between outside air collection and entry into the operating room.
5) Aerodynamic scenarios: where filtration is located + airflow regime
A) Filtration placement concepts
- Central AHU filters: duct cleanliness matters to prevent recontamination between AHU outlet and OR supply.
- Operating-room terminal filtration: for very stringent classes (e.g., H13/H14 referenced), robust final filtration near delivery is needed.
B) Airflow types: unidirectional vs turbulent (and implications)
- Unidirectional flow
- Parallel streams with similar velocity
- Homogeneous coverage of the operating field
- Typically required to achieve ISO 5 reliably
- Directional flow “vertical/horizontal”
- Mentioned as analogous to laminar flow hood behavior.
- Turbulent flow
- Creates mixing with ambient room air
- Contamination can return into the surgical field due to turbulence/mixing
- Discussed in relation to achieving higher ISO classes (e.g., ISO 7/ISO 8)
6) Air distribution must match the risk class and surgical field
Room designs are chosen based on:
- specific class
- nature of risk
- performance objectives
Examples discussed:
- Linear / older ceiling systems
- Deliver clean air to the surgical field
- Turbulence outside the ultra-clean zone
- Suspended/covered surgical zone ceiling systems
- Better protection of the ultra-clean zone overall
- Described as “laminar flow” at the highest level
7) Additional operational controls
(energy saving mode, qualification testing, pressure cascades)
A) Standby / reduced ventilation mode
- ORs may run reduced ventilation when unoccupied, then restart optimally at surgery start.
- Requires testing/verification to confirm performance at activation.
B) Classification parameters (particle counts)
- ISO 14644 limits depend on:
- number of particles per cubic meter
- particle diameter
- Example referenced:
- ISO 5 thresholds such as 10,000 particles >0.3 µm and 3,500 >0.5 µm.
C) Microbiological aspect (M values)
- M1 / M10 microbiological cleanliness categories were discussed.
- Relationship to airflow regime:
- under laminar/unidirectional conditions: stricter expectations (near “no microorganisms”)
- under turbulent conditions: less strict (e.g., M10 referenced)
D) Elimination kinetics
- Stress on elimination kinetics:
- introduce a pollutant → measure the time to remove 90%
- Practical implication:
- helps determine the time between operations for returning to target classification.
E) Pressure cascade (overpressure)
- Overpressure helps maintain airflow direction:
- cleanroom → airlock → pushes outward.
- Magnitude cited: 15 Pascals ± 5
- too low (e.g., 10 Pa) may fail to offset door openings.
- Purpose: prevent exogenous contaminants from entering between protective spaces.
F) Periodic checks
- Because contamination can be resuspended if AHU/duct conditions degrade, periodic validation and checks are emphasized.
Q&A points related to Presentation 1 (key themes)
- If elimination kinetics weren’t measured during ISO 5 qualification
- Laminar flow may remove contaminants faster, but kinetics are still recommended to identify dead zones under less-than-ideal real conditions.
- Return air position (bottom vs top)
- Returns must match the flow design; avoid drawing supply air back from the ceiling.
- Cutting off returns can reduce purge/kinetics.
- Filtration class selection across particle sizes
- Compliance may be assessed with one diameter basis, but monitoring multiple diameters can detect drift/leaks.
- Microbiology non-compliance despite compliant ISO particle/aerodynamics
- If ISO 5 truly holds for particles/aerodynamics, the likely cause is less about airflow itself and more about other pathways (sampling, cleaning, or very small biological particles).
Presentation 2 — Professor Jean-Christophe Lucet
Clinical risk approach: airborne infection risk across care settings
1) Where airborne ventilation questions arise
Ventilation/airborne infection control targets removal/prevention via:
- Immunological barriers (ICU, hematology, transplant)
- Goal: protect patients from incoming air using positive pressure
- Physical barriers (operating rooms, burn units)
- Goal: protect the patient site and minimize outgoing contamination using appropriate pressure regimes
- High-risk airborne infectious agents
- Emphasized examples: tuberculosis, measles, chickenpox
- Also mentions other airborne viruses, highlighted during COVID-19.
2) Main clinical objectives
- Reduce exposure or spread using:
- positive pressure (patient protection from incoming air) in immunocompromised contexts
- negative pressure (prevent escape of infectious agents) in infectious contexts
3) Regulatory landscape (as stated)
- No specific broad regulations were described that require hospital-specific air treatment beyond the labor-code baseline ventilation.
- Example baseline given: 60 m³/h per person.
- Hospitals rely on:
- reference standards/documents, notably AFNOR/EN air hygiene standards (linked to the earlier ISO 14644 risk-based framework).
4) Four “risk levels” and criteria
Risk classes are based on criteria including:
- zone delimitation
- cleanliness/particle elimination targets
- microbiological cleanliness targets
- pressure
- airflow regime
- procedure-specific cleanliness requirements
5) Operating rooms: ISO 5 vs ISO 7 and evidence on SSI
- ORs are mostly classified around risk level 3, with exceptions.
- The debate summarized:
- ISO 5 is typically associated with laminar flow
- ISO 7 with turbulent flow
- Key message from WHO analysis/studies:
- For certain prosthetic orthopedic procedures, evidence suggests no difference in surgical site infection risk between laminar and turbulent ventilation.
- Limitations acknowledged: reliance on observational/registry data.
- Important nuance:
- Real OR airflow is disrupted by humans, obstacles, patient warming, and staff movement—so qualification conditions may not reflect true risk.
6) Real-world airborne contamination mechanism (example)
- An outbreak pattern was described where aerosols/mist from thermal generators entered the laminar flow environment, deposited, and infections appeared later.
7) Recommendations evolution (prosthetic surgery and laminar flow)
- WHO/other guidance evolved over time:
- earlier advice was against laminar flow for certain cases
- later French guidance (SF2H) recommended unidirectional airflow in 2015
- updated in 2018 to allow greater flexibility
- However, an AFNOR standard remains a regulatory reference requiring certain ISO levels for specific procedures.
8) Intensive care: pressure and air change rate guidance
- Pre-COVID consensus points cited:
- for some risks (e.g., aspergillosis): positive pressure + high air changes
- for airborne infection risks: negative pressure + high air change volumes/hour
- COVID-era discussion (2021) for critical care included:
- 8–10 air changes per hour
- absolute filtration
- positive pressure relative to the corridor at a specified value (example given ~10 vs corridor)
- ability to switch toward isobaric conditions when maintaining overpressure is undesirable
- use of airlock-capable rooms
9) Conventional wards: minimal ventilation and CO₂-based confinement control
- Risk level 1:
- described as not requiring air renewal in the AFNOR framing.
- Practice issue:
- many rooms ventilate little (some use small mechanical ventilation in bathrooms).
- CO₂ used as a proxy for crowding:
- examples given for acceptable CO₂ thresholds
- to stay below thresholds, air exchange rates may need to exceed common “two volumes” practice.
- Sustainability/energy constraints (e.g., fewer window openings) increase pressure to design ventilation that compensates.
10) Pandemic decision-making: coverage vs whole-hospital upgrades
Key decision: gradual upgrades in parts of the hospital vs full facility upgrades.
- Because risk is expected but uncertainty remains, choices must balance:
- complexity and cost
- feasibility and maintainability
- likely effectiveness.
11) Clinical conclusions from this perspective
- Operating rooms
- ISO 5 is unlikely to clearly outperform ISO 7 based on current evidence and limited high-level randomized trials.
- ISO 5 is expensive and difficult to maintain.
- Ventilation heterogeneity and uneven application have historically reduced real-world benefits.
- Intensive care
- described need: 8 volumes ± 2 of air exchange per unit
- reversing pressure adds complexity; pressure cascades must be validated.
Presentation 3 — Emmanuel Vanoly (Dassault Systèmes)
Simulation-based environmental control
1) Why simulation is used
Airborne transmission was framed as driven by three phenomena:
- Emission: contaminated particles emitted by a person
- Propagation: spread through ventilated environments
- Deposition / resuspension: settling on surfaces or release due to activities
Limitations:
- Laboratory testing
- strong measurement control
- but cannot replicate realistic hospital ventilation/architecture
- Real hospital testing
- complex: isolating rooms, delaying operations, instrument rooms, etc.
Therefore: 3D simulation (validated tools) is used as a compromise.
2) What simulations model include
- Person/patient aerosol emission (including breathing/cough realism)
- Hospital architecture
- Ventilation system layout and airflow patterns
- Heat emission interactions affecting plume behavior
Study A (2020, Bichat Hospital / ICU)
Negative pressure, masks, Optiflow
Goal
- quantify particle emission in negative pressure areas (with/without ventilatory support)
- estimate healthcare worker exposure risk
Approach
- virtual mannequin with detailed upper respiratory anatomy (trachea, glottis, mouth/teeth)
- validate airflow assumptions against real tests (Ecole Polytechnique)
Key findings
- Ceiling-mounted supply “skims and cools” but can worsen aerosol dispersion control.
- Negative pressure + door gaps can create suction patterns that allow plumes to rise and disperse.
- Extraction near the ceiling may not effectively contain particles outside its local influence.
- After ~1 minute, extraction removes only about half of particles (as described).
Mobile air treatment system (Plasmar, ~1000 m³/h)
- Placement matters:
- under extraction can trap particles, reducing extraction performance (e.g., <20% extracted after a minute)
- opposite the door to guide airflow toward extraction improves capture vs a bed-only baseline.
Study B (early 2021, Saint-Joseph Hospital ICU)
Vent layout optimization
Problem
- episodes of airborne contamination; rooms looked similar but outcomes differed.
Method
- simulation of airflow and particle accumulation based on subtle vent-position/geometric differences.
Findings
- Small variations in vent spacing relative to patient position and between vents can strongly affect:
- where particles accumulate
- how quickly rooms decontaminate
- Experimental aerosol tests confirmed simulation dynamics.
Intervention
- redesign airflow patterns without changing the ventilation rate setting
- aim: direct particles back toward exhaust vents and reduce dead zones
- targeted room layouts (including triangular concept + exhaust close to patient)
- simulations showed improved decontamination when extraction captures the plume before it disperses.
Study C (PACU at Pitié-Salpêtrière, Oct 2020 → Jan 2021)
Unexpected particle propagation in COVID zones
Scenario
- PACU planned COVID zones and patient separation, but unexpected particle spread occurred.
Simulation revealed
- cross-shaped ceiling airflow spreading to distant zones within tens of seconds
- near-direct transmission to two patients positioned along the problematic airflow routes.
Actions
- rapid simulation-led modifications within days
- aerosol counting tests and further university verification
Engineering changes
- break the cross-shaped airflow pattern:
- replace ceiling fins with a perforated “box/sheet” to reduce velocities and disperse between zones
- partition between patients
- add extraction vents behind patients connected to ducting
- tested slight negative vs slight positive pressure
- negative pressure performed better, while positive pressure worsened efficiency and increased escape risk.
Outcome
- modifications became permanent and extended to other units (including maternity-related contexts) based on team acceptance.
Study D
Surface contamination prediction + weather-driven deposition
Goal
- predict contaminated surfaces (PCR positive/negative) using particle deposition (“film thickness”) simulation.
Method
- simulate ICU rooms including slightly open windows to counter pressure effects
- compare predicted accumulation locations to real sampling surfaces:
- bed rail, mask area, tablet, syringe, scop, etc.
Field anomaly
- a sudden switch from all-negative to all-positive sampling over a few days across rooms on one hospital side.
Hypothesis/mechanism
- external weather factor (wind direction) interacting with building geometry and window openings:
- wind shifted (easterly → northwesterly) during the relevant date range
- airflow currents changed deposition locations (from window/floor toward bed rails/equipment)
- simulation reproduced deposition shift and explained the sampling positivity pattern.
Q&A points (high-level)
- Purifier placement and extraction over time
- added value depends on temporal extraction dynamics and placement relative to bed/door; longer extraction might change differences but likely not overturn conclusions.
- Risk of particles escaping into corridors
- plausible if doors/windows open; with doors closed and adequate room airflow, corridor spread is less likely (top-blown unit placement matters).
- Pressure troubleshooting in operating rooms
- pressure depends on fresh air vs recirculated flow and “blowing” vs induced effects (“Hermes factor” referenced)
- door openings or changing airflow distributions can reduce overpressure.
- Microbiology non-compliance despite ISO 5
- if particle/aerodynamics ISO 5 is truly met, likely cause is elsewhere (sampling/cleaning or other contamination pathways rather than controlled airflow).
- Role of UVC
- effectiveness depends on delivered dose and distance; practical constraints make large-surface UVC difficult compared with filtration/clean-air strategies and procedural controls.
- Lessons for vent placement in ICU
- extraction close to the patient appears beneficial
- supply diffuser geometry and types vary; no single universal rule
- maintenance drift causes many facilities to deviate from design flows—ongoing measurement/monitoring is critical.